RMS Pump, Inc.
Multnomah County PM
2610 Fairview Parkway
Fairview, OR 97024
(503) 665-8101
lmcquaw@rmspump.com
Multnomah County PM
Preventative Maintenance Record
Technician Notes
Noise pass. Couplings good - Lovejoy with wrap-around insert. Will need scheduled shutdown for panel and pump.
Readings
| Reading | Point 1 | Point 2 | Point 3 | Point 4 | Point 5 | Point 6 | Point 7 | Point 8 |
|---|---|---|---|---|---|---|---|---|
| Mils | A.6-1.0 | B.36-.56 | C.28-.35 | D.2-.42 | E.62-.86 | F.35-.46 | G.18-.42 | H.18-.36 |
| In/sec | A.07 | B.04 | C.04 | D.02 | E.07 | F.05 | G.03 | H.02 |
| G's Peak | A.46 | B.3 | C.56 | D.2 | E.57 | F.22 | G.49 | H.27 |
| Temp | PT108.6° | PM139.4° | PB123° | MT59.3° | MM54.1° | MB | A | B |
| RPM at shaft | 1770 |
|---|---|
| Ambient Temp. | 75.2° |
| Amps | 32.6 / 34.2 / 33.2 |
| Volts | 454 / 454 / 455 |
| Meg (resistance) | |
| Hours (runtime) | |
| Inlet pressure | 49 |
| Discharge pressure | 61 |
| Noise | Pass |
| Controller Temp | 80-96° |
Pump Information
Sulzer / Paco Chiller 6 pump
cat#29401281450012882EE ser 61575401B
GPM 770 TDH 100 imp 10.75
Diffuser Sulzer cat# PSD6050-125 stock# 61851201B
cat#29401281450012882EE ser 61575401B
GPM 770 TDH 100 imp 10.75
Diffuser Sulzer cat# PSD6050-125 stock# 61851201B
Motor Information
Baldor cat# VHECP4104T spec 10F352X207G1 HP 30 V 230/460 A 72/36 RPM 1770 frame 286HP hz 60 SF 1.15; PH 3; code B; des B; class F; NEMA 94.1%; PF 81% enc TEFC ser C0502150043 DE 6311; ODE 6309
Controller Information
B119.9 CHWP14 MCC A Bucket 04 VFD
Valve Information
Suction and discharge isolation