RMS Pump, Inc.
Multnomah County PM
2610 Fairview Parkway
Fairview, OR 97024
(503) 665-8101
lmcquaw@rmspump.com
Multnomah County PM
Preventative Maintenance Record
Technician Notes
Needs new coupling insert. Lower bearing noise at motor - greased. Lots of vibration.
Readings
| Reading | Point A | Point B | Point C | Point D | Point E | Point F | Point G | Point H |
|---|---|---|---|---|---|---|---|---|
| Mils | 1.2-1.6 | .44-.68 | .3-.7 | .32-.7 | 4.6-5.2 | 1.7-1.9 | .3-.5 | .9-1.1 |
| In/sec | .15 | .05 | .05 | .04 | .5 | .18 | .03 | .1 |
| G's Peak | 1.0 | .4 | .64 | .44 | 1.0 | .34 | .4 | .3 |
| Temp | 103.1° | 124.1° | 104° | 82.7° | 77.1° |
| RPM at shaft | 1770 |
|---|---|
| Ambient Temp. | 79.5° |
| Amps | 32.6 / 32.4 / 29.2 |
| Volts | 477 / 475 / 477 |
| Meg (resistance) | |
| Hours (runtime) | |
| Inlet pressure | 35 |
| Discharge pressure | 55 |
| Noise | Fail (see notes) |
| Controller Temp |
Pump Information
Sulzer / Paco Chiller 5 pump
cat#29301221450012882EE ser 61575402B
GPM 905 TDH 90 imp 9.85
Diffuser Sulzer cat# PSD808-125 stock# 61851202A
cat#29301221450012882EE ser 61575402B
GPM 905 TDH 90 imp 9.85
Diffuser Sulzer cat# PSD808-125 stock# 61851202A
Motor Information
Baldor cat# VHECP4104T spec 10F352X207G1 HP 30 V 230/460 A 72/36 RPM 1770 frame 286HP hz 60 SF 1.15; PH 3; code H; des B; class F; NEMA 94.1% enc TEFC ser C0502150038 DE 6311; ODE 6309
Controller Information
Disconnect
Valve Information
Suction and discharge isolation