RMS Pump, Inc.

Multnomah County PM

2610 Fairview Parkway
Fairview, OR 97024
(503) 665-8101
lmcquaw@rmspump.com
Multnomah County PM

Preventative Maintenance Record

Prepared November 20, 2026 5:30 AM

Client
Multnomah County
Date
August 27, 2026
Pump
Pump 2
Building
Justice Center - Multnomah County Detention Center (MCDC)

Technician Notes

Running 29.9%.
System has expansion tank (no info). Tank good. VFDs vacuumed. VFD running Loc and Rem. Possible need ground rings on motors. Sound of water hammer. VFD program needs checked. Needs bigger pressure tank. May need shaft grounds. Noise fail. Loud for running %s.

Readings

ReadingPoint 1Point 2Point 3Point 4Point 5Point 6Point 7Point 8
MilsA2.8-3.2B1.6-1.8C.7-.9D10-12E2.8-4.0F.16-.18G H 
In/secA.52B.19C.09D1.8E.32F.08G H 
G's PeakA.6B.48 (V)C.52D.8E.36F.22G H 
TempPT PM PB MT87.4°MM98.6°MB80°A B 
RPM at shaft 
Ambient Temp. 
Amps2.1 / 2.0 / 2.2
Volts476 / 478 / 478
Meg (resistance) 
Hours (runtime) 
Inlet pressure 
Discharge pressure 
NoiseFail (see notes)
Controller Temp 

Pump Information

Goulds domestic booster system - possible different floors.
Retagged by Ferguson
Size 2.5 x 2.5
Model 335VBB17L6DA
Goulds tag 335VBB0K2A
Job #160800
362 PSI max

Motor Information

Baldor cat# VM3312T spec 37B103Y511H1 (V) FR 213TC HP 10 V 208-230/460 A 25.6-23.2/11.6 RPM 3490 Hz 60 PH 3; SF 1.15; code F; des B; class B; eff 88.5%; PF 91; rating 40 amb-cont; enc OPSB; DE 6307; ODE 6206; ser F0505044065

Controller Information

Panel VFD FNW H2O FloPro model VMS-3410-R; manu. 08/05. Aquavar VFD 20 HP 3 ph I/O 28 A. Texas instrument ser# 24-03-04-11906.

Valve Information

Not provided.