Multnomah County PM
Preventative Maintenance Record
Technician Notes
Electrical fire system needs tested while running.
Multiple loose connections found; fuse holder broken.
Coupling OK.
Will need to schedule shutdown to service panels.
Multiple loose connections found; fuse holder broken.
Coupling OK.
Will need to schedule shutdown to service panels.
Readings
| Reading | Point A | Point B | Point C | Point D | Point E | Point F | Point G | Point H |
|---|---|---|---|---|---|---|---|---|
| Mils | ||||||||
| In/sec | ||||||||
| G's Peak | ||||||||
| Temp |
| RPM at shaft | 3520 |
|---|---|
| Ambient Temp. | |
| Amps | 69-70.5 |
| Volts | 478 / 481 / 480 |
| Meg (resistance) | |
| Hours (runtime) | |
| Inlet pressure | 78 |
| Discharge pressure | 200 |
| Noise | |
| Controller Temp | 69-75° |
Pump Information
Fairbanks Morse
SER K3H1013178
4" 1 stage
Fig 5876 Fire Pump
GPM 750 @ 117 PSI
Max suction 71 PSI
Max BHP 81.4
3520 RPM
Net Pressure max 140.4 @ 150%; 76 PSI
8.6" Imp Dia
SER K3H1013178
4" 1 stage
Fig 5876 Fire Pump
GPM 750 @ 117 PSI
Max suction 71 PSI
Max BHP 81.4
3520 RPM
Net Pressure max 140.4 @ 150%; 76 PSI
8.6" Imp Dia
Motor Information
Lincoln
frame 364TS ser 2468632
RPM 3520 HP 75 Ph 3 V 230/460 A 176/88 Hz 60
SF 1.15 Lincoln Code TV296 Ins B max Amb 40C
Eff 88.5 Time Rating Cont Nema Code D Nema Design [unclear]
frame 364TS ser 2468632
RPM 3520 HP 75 Ph 3 V 230/460 A 176/88 Hz 60
SF 1.15 Lincoln Code TV296 Ins B max Amb 40C
Eff 88.5 Time Rating Cont Nema Code D Nema Design [unclear]
Controller Information
Firetrol
Flag 5876 Fire Pump [best read]
Flag 5876 Fire Pump [best read]
Valve Information
Not provided.