Technician Notes
Motor Lower bearing noise - greased
Will need to schedule shutdown to meg motor, service panel, and exercise valves.
VFD program needs checked.
Patch board loose in panel.
Will need to schedule shutdown to meg motor, service panel, and exercise valves.
VFD program needs checked.
Patch board loose in panel.
Readings
| Reading | Point A | Point B | Point C | Point D | Point E | Point F | Point G | Point H |
|---|---|---|---|---|---|---|---|---|
| Mils | .30-.40 | .38-.52 | .5-.8 | .09-.22 | .28-.50 | .47-.82 | ||
| In/sec | .06-.07 | .06-.07 | .07-.09 | .02-.03 | .05-.06 | .06-.09 | ||
| G's Peak | .22-.26 | .28-.34 | .36-.38 | .18-.2 | 31-.33 | 42-.64 | ||
| Temp | 60° | 64° | 100° | 88° |
| RPM at shaft | |
|---|---|
| Ambient Temp. | 70-74° |
| Amps | .5 / .3 / .7 |
| Volts | 479 / 477 / 478 |
| Meg (resistance) | |
| Hours (runtime) | |
| Inlet pressure | |
| Discharge pressure | |
| Noise | |
| Controller Temp |
Pump Information
G&L Pumps SSV
cat#4SVBK4IC PSI MAX 350 TEMP MAX 250F
cat#4SVBK4IC PSI MAX 350 TEMP MAX 250F
Motor Information
Baldor Super E
cat#CEM3616T spec 36A002S428G1 HP 7.5 V 230/460 A 16.8/8.4 RPM 3450 frame 184TC hz 60 ph 3 sf 1.15 code L des A class F eff 89.5% pf 93% rating 40C AMB-CONT enc TEFC ser F2502201492 de 6206 ode 6205
cat#CEM3616T spec 36A002S428G1 HP 7.5 V 230/460 A 16.8/8.4 RPM 3450 frame 184TC hz 60 ph 3 sf 1.15 code L des A class F eff 89.5% pf 93% rating 40C AMB-CONT enc TEFC ser F2502201492 de 6206 ode 6205
Controller Information
FNW H2O FloPro Duplex VFD model VMS-2210-R-VFD s/n 160794-01 manuf date 08/05
Inertia controls Duplex acuavar power input 18.2 output 15HP freq input/output 0-60HZ v input 480/3PH output 0-480/3PH a 22 ser 30-29003
Inertia controls Duplex acuavar power input 18.2 output 15HP freq input/output 0-60HZ v input 480/3PH output 0-480/3PH a 22 ser 30-29003
Valve Information
Suction and discharge isolation