Preventative Maintenance Record

Prepared September 22, 2026 7:58 AM

Client
Multnomah County
Date
August 27, 2026

Technician Notes

Motor Lower bearing noise - greased
Will need to schedule shutdown to meg motor, service panel, and exercise valves.
VFD program needs checked.
Patch board loose in panel.

Readings

ReadingPoint APoint BPoint CPoint DPoint EPoint FPoint GPoint H
Mils.30-.40.38-.52.5-.8.09-.22.28-.50.47-.82  
In/sec.06-.07.06-.07.07-.09.02-.03.05-.06.06-.09  
G's Peak.22-.26.28-.34.36-.38.18-.231-.3342-.64  
Temp60°64°100°88°    
RPM at shaft 
Ambient Temp.70-74°
Amps.5 / .3 / .7
Volts479 / 477 / 478
Meg (resistance) 
Hours (runtime) 
Inlet pressure 
Discharge pressure 
Noise 
Controller Temp 

Pump Information

G&L Pumps SSV
cat#4SVBK4IC PSI MAX 350 TEMP MAX 250F

Motor Information

Baldor Super E
cat#CEM3616T spec 36A002S428G1 HP 7.5 V 230/460 A 16.8/8.4 RPM 3450 frame 184TC hz 60 ph 3 sf 1.15 code L des A class F eff 89.5% pf 93% rating 40C AMB-CONT enc TEFC ser F2502201492 de 6206 ode 6205

Controller Information

FNW H2O FloPro Duplex VFD model VMS-2210-R-VFD s/n 160794-01 manuf date 08/05
Inertia controls Duplex acuavar power input 18.2 output 15HP freq input/output 0-60HZ v input 480/3PH output 0-480/3PH a 22 ser 30-29003

Valve Information

Suction and discharge isolation