Preventative Maintenance Record

Prepared September 22, 2026 7:59 AM

Client
Multnomah County
Date
August 27, 2026

Technician Notes

Motor Lower bearing noise - greased
Will need to schedule shutdown to meg motor, service panel, and exercise valves.

Readings

ReadingPoint APoint BPoint CPoint DPoint EPoint FPoint GPoint H
Mils.22-.5.3-.5.5-.9.14-.2.24-.56.36-.81  
In/sec.02-.03.02-.04.04-.06.02-.03.01-.03.02-.04  
G's Peak.08-.09.24-.32.26.01.35-.39.24  
Temp70.7°84.5°82°     
RPM at shaftIATOS
Ambient Temp.70-74f°
Amps3.5,3.5,3.5
Volts480,477,480
Meg (resistance)IATOS
Hours (runtime)Missed
Inlet pressure63
Discharge pressure176-184
NoiseFail
Controller Temp73-78°

Pump Information

G&L Pumps SSV
cat#4SVBK4IC PSI MAX 350 TEMP MAX 250F

Motor Information

Baldor Super E
cat#CEM3616T spec 36A002S428G1 HP 7.5 V 230/460 A 16.8/8.4 RPM 3450 frame 184TC hz 60 ph 3 sf 1.15 code L des A class F eff 89.5% pf 93% rating 40C AMB-CONT enc TEFC ser F2502201327 de 6206 ode 6205

Controller Information

FNW H2O FloPro Duplex VFD model VMS-2210-R-VFD s/n 160794-01 manuf date 08/05
Inertia controls Duplex acuavar power input 18.2 output 15HP freq input/output 0-60HZ v input 480/3PH output 0-480/3PH a 22 ser 30-29003

Valve Information

Suction and discharge isolation