If your browser blocks automatic tab closing, close this tab manually.

RMS Pump, Inc.

Multnomah County PM

2610 Fairview Parkway
Fairview, OR 97024
(503) 665-8101
lmcquaw@rmspump.com
Multnomah County PM

Preventative Maintenance Record

Prepared November 20, 2026 5:30 AM

Client
Multnomah County
Date
August 27, 2026
Pump
P-1
Building
Justice Center - Multnomah County Detention Center (MCDC)

Technician Notes

Motor Lower bearing noise - greased
Will need to schedule shutdown to meg motor, service panel, and exercise valves.

Readings

ReadingPoint 1Point 2Point 3Point 4Point 5Point 6Point 7Point 8
MilsA.22-.5B.3-.5C.5-.9D.14-.2E.24-.56F.36-.81G H 
In/secA.02-.03B.02-.04C.04-.06D.02-.03E.01-.03F.02-.04G H 
G's PeakA.08-.09B.24-.32C.26D.01E.35-.39F.24G H 
TempPT70.7°PM84.5°PB82°MT MM MB A B 
RPM at shaftIATOS
Ambient Temp.70-74f°
Amps3.5,3.5,3.5
Volts480,477,480
Meg (resistance)IATOS
Hours (runtime)Missed
Inlet pressure63
Discharge pressure176-184
NoiseFail
Controller Temp73-78°

Pump Information

G&L Pumps SSV
cat#4SVBK4IC PSI MAX 350 TEMP MAX 250F

Motor Information

Baldor Super E
cat#CEM3616T spec 36A002S428G1 HP 7.5 V 230/460 A 16.8/8.4 RPM 3450 frame 184TC hz 60 ph 3 sf 1.15 code L des A class F eff 89.5% pf 93% rating 40C AMB-CONT enc TEFC ser F2502201327 de 6206 ode 6205

Controller Information

FNW H2O FloPro Duplex VFD model VMS-2210-R-VFD s/n 160794-01 manuf date 08/05
Inertia controls Duplex acuavar power input 18.2 output 15HP freq input/output 0-60HZ v input 480/3PH output 0-480/3PH a 22 ser 30-29003

Valve Information

Suction and discharge isolation