RMS Pump, Inc.
Multnomah County PM
2610 Fairview Parkway
Fairview, OR 97024
(503) 665-8101
lmcquaw@rmspump.com
Multnomah County PM
Preventative Maintenance Record
Technician Notes
Motor Lower bearing noise - greased
Will need to schedule shutdown to meg motor, service panel, and exercise valves.
Will need to schedule shutdown to meg motor, service panel, and exercise valves.
Readings
| Reading | Point A | Point B | Point C | Point D | Point E | Point F | Point G | Point H |
|---|---|---|---|---|---|---|---|---|
| Mils | .22-.5 | .3-.5 | .5-.9 | .14-.2 | .24-.56 | .36-.81 | ||
| In/sec | .02-.03 | .02-.04 | .04-.06 | .02-.03 | .01-.03 | .02-.04 | ||
| G's Peak | .08-.09 | .24-.32 | .26 | .01 | .35-.39 | .24 | ||
| Temp | 70.7° | 84.5° | 82° |
| RPM at shaft | IATOS |
|---|---|
| Ambient Temp. | 70-74f° |
| Amps | 3.5,3.5,3.5 |
| Volts | 480,477,480 |
| Meg (resistance) | IATOS |
| Hours (runtime) | Missed |
| Inlet pressure | 63 |
| Discharge pressure | 176-184 |
| Noise | Fail |
| Controller Temp | 73-78° |
Pump Information
G&L Pumps SSV
cat#4SVBK4IC PSI MAX 350 TEMP MAX 250F
cat#4SVBK4IC PSI MAX 350 TEMP MAX 250F
Motor Information
Baldor Super E
cat#CEM3616T spec 36A002S428G1 HP 7.5 V 230/460 A 16.8/8.4 RPM 3450 frame 184TC hz 60 ph 3 sf 1.15 code L des A class F eff 89.5% pf 93% rating 40C AMB-CONT enc TEFC ser F2502201327 de 6206 ode 6205
cat#CEM3616T spec 36A002S428G1 HP 7.5 V 230/460 A 16.8/8.4 RPM 3450 frame 184TC hz 60 ph 3 sf 1.15 code L des A class F eff 89.5% pf 93% rating 40C AMB-CONT enc TEFC ser F2502201327 de 6206 ode 6205
Controller Information
FNW H2O FloPro Duplex VFD model VMS-2210-R-VFD s/n 160794-01 manuf date 08/05
Inertia controls Duplex acuavar power input 18.2 output 15HP freq input/output 0-60HZ v input 480/3PH output 0-480/3PH a 22 ser 30-29003
Inertia controls Duplex acuavar power input 18.2 output 15HP freq input/output 0-60HZ v input 480/3PH output 0-480/3PH a 22 ser 30-29003
Valve Information
Suction and discharge isolation