RMS Pump, Inc.
Multnomah County PM
2610 Fairview Parkway
Fairview, OR 97024
(503) 665-8101
lmcquaw@rmspump.com
Multnomah County PM
Preventative Maintenance Record
Technician Notes
Running 100%. Sound pass. Seal pass.
Readings
| Reading | Point 1 | Point 2 | Point 3 | Point 4 | Point 5 | Point 6 | Point 7 | Point 8 |
|---|---|---|---|---|---|---|---|---|
| Mils | A.44-.48 (V) | B.48-.52 | C.06-.07 | D.08-.09 | E | F | G | H |
| In/sec | A.05 | B.05 | C.02 | D.03 | E | F | G | H |
| G's Peak | A.15 | B.18 | C.17 | D.27 | E | F | G | H |
| Temp | PT | PM | PB | MT84.2° | MM97.8° | MB79.8° | A | B |
| RPM at shaft | |
|---|---|
| Ambient Temp. | 72° |
| Amps | |
| Volts | |
| Meg (resistance) | |
| Hours (runtime) | |
| Inlet pressure | 26 |
| Discharge pressure | 42 |
| Noise | Pass |
| Controller Temp |
Pump Information
Taco radiant system
AMTROL tank model SX30V
Part# 118-27
Tank date 01/28/2020
Max PSI 100; max temp 240; charge 12 PSI
AMTROL tank model SX30V
Part# 118-27
Tank date 01/28/2020
Max PSI 100; max temp 240; charge 12 PSI
Motor Information
Baldor
Controller Information
ABB VFD
Valve Information
Suction and discharge valves