RMS Pump, Inc.
Multnomah County PM
2610 Fairview Parkway
Fairview, OR 97024
(503) 665-8101
lmcquaw@rmspump.com
Multnomah County PM
Preventative Maintenance Record
Technician Notes
Coupling Lovejoy flex. TJE pass. Noise pass. Sound good. Guard is held down by frame.
Readings
| Reading | Point 1 | Point 2 | Point 3 | Point 4 | Point 5 | Point 6 | Point 7 | Point 8 |
|---|---|---|---|---|---|---|---|---|
| Mils | A.22-.32 | B.1-.18 | C.20-.43 | D.2-.32 | E.24-.3 | F.22-.3 | G.24-.30 | H.3-.44 |
| In/sec | A.07 | B.06 | C.09 | D.05 | E.07 | F.06 | G.08 | H.06 |
| G's Peak | A.7 | B.34 | C.2 | D | E.78 | F.42 | G.7 | H.94 |
| Temp | PT107° | PM149.7° | PB91.9° | MT142.1° | MM105.2° | MB81.6° | A | B |
| RPM at shaft | |
|---|---|
| Ambient Temp. | 79.7° |
| Amps | 6.6 / 7.2 / 8.1 |
| Volts | 480 / 479 / 478 |
| Meg (resistance) | |
| Hours (runtime) | |
| Inlet pressure | 7 |
| Discharge pressure | 47 |
| Noise | Pass |
| Controller Temp |
Pump Information
Berkley condenser water pump
10SWM / B119 CWP.23 / SMCC 9D Bucket #19
B 1-1/2 ERL / 6-16806; impeller 10.43
Serves 11th floor telecom room; stairwell access; also 2nd floor pumps
10SWM / B119 CWP.23 / SMCC 9D Bucket #19
B 1-1/2 ERL / 6-16806; impeller 10.43
Serves 11th floor telecom room; stairwell access; also 2nd floor pumps
Motor Information
Baldor M3311T spec 36B103T848 HP 7.5 V 208-230/460 A 21.7-20/10 RPM 1750 frame 213T Hz 60 enc OPSB ser F0907242108 PH 3; SF 1.15; code J; des A; class B; eff 88.5%; PF 79% DE 6207; ODE 6205
Controller Information
SMCC 9D Bucket #19
Valve Information
Suction and discharge isolation