RMS Pump, Inc.
Multnomah County PM
2610 Fairview Parkway
Fairview, OR 97024
(503) 665-8101
lmcquaw@rmspump.com
Multnomah County PM
Preventative Maintenance Record
Technician Notes
Lovejoy L100 coupling OK. Sound/operation good. L3 has higher amp draw. This motor may need replacing soon due to failing leg.
Readings
| Reading | Point 1 | Point 2 | Point 3 | Point 4 | Point 5 | Point 6 | Point 7 | Point 8 |
|---|---|---|---|---|---|---|---|---|
| Mils | A.15-.26 | B.3-.36 | C.44-.48 | D.36-.40 | E.44-.48 | F.52-.54 | G.52-.58 | H.62-.68 |
| In/sec | A.05 | B.05 | C.06 | D.04 | E.07 | F.07 | G.07 | H.07 |
| G's Peak | A.25 | B.22 | C.26 | D.14 | E.3 | F.22 | G.26 | H.23 |
| Temp | PT110.0° | PM140.5° | PB123.8° | MT102.3° | MM91.7° | MB76.4° | A | B |
| RPM at shaft | |
|---|---|
| Ambient Temp. | 76.5° |
| Amps | 7.5 / 7.2 / 9.3 |
| Volts | 475 / 478 / 477 |
| Meg (resistance) | |
| Hours (runtime) | |
| Inlet pressure | N/A |
| Discharge pressure | 42 |
| Noise | Pass |
| Controller Temp |
Pump Information
Paco Condenser water pump
model Paco
cat# 11 20121-73301
ser B2LZAHP09424
GPM 40
TDH 112
imp 11"
model Paco
cat# 11 20121-73301
ser B2LZAHP09424
GPM 40
TDH 112
imp 11"
Motor Information
Baldor cat# EM3311T spec 37F614X635 FR 213T HP 7.5 V 230/460 A 18.6/9.3 RPM 1760 Hz 60 PH 3 enc DP ser F1094 ; class B; SF 1.15; des B; code H; eff 91% DE 6307; ODE 6206
Controller Information
B119 CWP.10; disconnect
Valve Information
Suction and discharge isolation